(Advanced) Parameter Details; A103 Cont. & A105 A108 65
10V
B
A
Parameter A103 vs FM+ Output
V (FM+)
0
Fig. 19.18
A105
Relay 1 (R1C,R1B,R1A terminals
on TM2)
0000: Run
0001: Frequency Reached (Target Frequency)
(Frequency Reference ± A108)
0002: Set Frequency (A107 ± A108)
0003: Frequency Threshold Level (> A107)
Frequency Reached
0004: Frequency Threshold Level (< A107)
Frequency Reached
0005: Over-torque Threshold Level
0006: Fault
0007: Auto-restart
0008: Momentary AC Power Loss
0009: Emergency Stop Mode
0010: Coast-to-Stop Mode
0011: Motor Overload Protection
0012: Drive Overload Protection
0013: PID Feedback Signal Break
0014: Power On
0015: Under-torque Threshold Level
A106
Relay 2 (R2C,R2A terminals on
TM2)
A107
Output Frequency Detection
Level
0 400 Hz
A108
Frequency Reached Bandwidth
0 30 Hz