N3 Drive Operations Manual
(Advanced) Parameter Details; A105 – A108 Cont. & A111 - A118 68
Output Current
Over Torque
Output
(A105/A106 = 05)
A105 / A106 = 05 Over Torque Detection
(A126)
Over Torque
Activation Delay
Time (0 – 25 sec.)
(A125)
Over Torque
Detection Level
(100 – 200 %)
Fig. 19.23
Trip Prevention Selection
During Acceleration
0000: Enable Trip Prevention During
Acceleration
0001: Disable Trip Prevention During
Acceleration
Trip Prevention Level During
Acceleration
50% - 300% (based by Motor HP A003)
Trip Prevention Selection
During Deceleration
0000: Enable Trip Prevention During
Deceleration
0001: Disable Trip Prevention During
Deceleration
Trip Prevention Level During
Deceleration
50% - 300% (based by Motor HP A003)
Trip Prevention Selection in
Run Mode
0000: Enable Trip Prevention in Run Mode
0001: Disable Trip Prevention in Run Mode
Trip Prevention Level in Run
Mode
50% - 300% (based by Motor HP A003)
Trip Prevention Deceleration
Time Selection in Run Mode
0000: Trip Prevention Deceleration Time Set by
b008
0001: Trip Prevention Deceleration Time Set by
A118
Deceleration Time in Trip
Prevention Mode (sec.)
1.) If the acceleration time is set too short, the inverter will delay the acceleration time in order to prevent an over
current trip “OC-AS”.
2.) If the deceleration time is set too short, the inverter will delay the deceleration time in order to prevent an over
voltage of DC BUS trip ‘OC-C’.
3.) Some mechanical equipment such as presses, or a mechanical failure such as seizing due to insufficient
lubrication, varying loads, etc. will cause the inverter to trip. When the operating torque of the inverter exceeds
the setting of A116, the inverter will lower the output frequency at the deceleration time set by A117, and then
return to normal operating frequency after the torque level stabilizes.
Cont.