N3 Drive Operations Manual
(Advanced) Parameter Details; A181 81
A181: Is set to 1110 when the inverter is used with motors rated at 50Hz.
A181: Is set to 1111 when the inverter is used with motors rated at60Hz.
Note:
Motor parameters (A168 - A172) will be modified when in V/F control mode after a factory reset is performed.
Motor parameters (A168 - A172) will not be modified when in vector control mode after a factory reset is performed.
After a reset to factory setting, the Axxx parameters will become inaccessible. Parameter b011 must then be set to
0001 to enable access to the A parameters.
NOTES:
A181
Reset to the factory setting
1110: Reset to the 50Hz factory setting
1111: Reset to the 60Hz factory setting