N3 fault 
Replace control board
No 
Set up frequency command
Check inverter parameters
Is the frequency displayed on the 
digital operator ?
No 
Yes
Connect the motor and run
Any fault displays ? 
Yes
The inverter is faulty. 
Perform a detailed check.
No 
Yes
Inverter is functioning normally
No 
Fig. 22.1  Fault Display Troubleshooting Cont.
Initialize parameters
Specify operation control mode
Continue from previous page
Fwd or Rev LED 
flashing ?
Replace control board
Yes
Is there motor output voltage at 
terminals  U, V & W ?
Replace control board
No 
Yes
Does the control board 
function normally after 
replacement  ?
Yes
Are the output currents of each 
phase balanced ?
No