Chapter 4 Software Index
4-13
05-V/F command group
Function
Code No.
Description Range/Code
Factory
Setting
Remarks
05-00
Volts/Hz Curve Modification
(Torque Boost) (%)
0 ~ 30.0 10.0 *5
05-01
Motor No Load Current
(Amps AC)
-----
*5
05-02
Motor rated Slip Compensation
(%)
0.0 ~ 100.0 25.0 *5
05-03
v/f max voltage 220V series:170.0 ~ 264.0
440V series:323.0 ~528.0
*5
05-04 Maximum Frequency (Hz) 0. 20 ~ 400.00 50.00/60.00 *5
05-05
Maximum Frequency Voltage
Ratio (%)
0.0 ~ 100.0 100.0
*5
05-06 Medium Frequency (Hz) 0. 10 ~ 400.00 25.00/30.00 *5
05-07
Medium Frequency Voltage
Ratio (%)
0.0 ~ 100.0
50.0
*5
05-08 Minimum Frequency (Hz) 0. 10 ~ 400.00 0.50/0.60 *5
05-09
Minimum Frequency Voltage
Ratio (%)
0.0 ~ 100.0
1.0
*5
05-10
V/F Energy Saving Mode
0: Disabled
1: Controlled by MFIT at Energy Saving
0
*5
05-11 V/F Energy Saving Gain (%) 0 ~ 100 80 *5
05-12 V/F start Frequency 0.00 ~ 10.00 0.00 *5
06-Motor parameter group
Function
Code No.
Description Range/Code
Factory
Setting
Remarks
06-00 Motor Rated Voltage (VAC) ----- *4
06-01 Motor Rated Current (Amp AC) ----- *4
06-02 Motor Rated Power (kW) ----- *4
06-03 Motor Rated Speed (RPM) ----- *4
06-04 Motor Rated Frequency (Hz) ----- *4
06-05 Motor Parameter Auto Tuning
0Invalid
1Valid
0
06-06 Stator Resistance (Ohms) ----- *3*4
06-07 Rotor Resistance (Ohms) ----- *3*4
06-08 Equivalent Inductance (mH) ----- *3*4
06-09 Magnetizing Current (AmpsAC) ----- *3*4
06-10 Ferrite Loss Conductance (gm) ----- *3*4
06-11
Low-frequency compensation
Gain
0 ~ 100 30

Table of Contents