Chapter 4 Software Index
4-58
(C) Auto_Run Mode for Single Cycle (13-00 = 3, 6)
The speed of final step will be held to run.
For example:
13-00 = 3 (or 6)
Panel Frequency (3-01) =15 Hz 13-01=30Hz 13-02=50Hz 13-15=20Hz
13-16=20s 13-17=25s 13-18=30s 13-31=40s
13-32=1 13-33=1 13-34 = 1 13-47=1(FWD)
13-04~13-15=0Hz , 13-20 ~ 13-30=0s , 13-35 ~ 13-46 0
Note:13-00 = 1~3 : If the inverter stops and re-starts, it will continue running from the unfinished
step, according to the setting of 13-00.
= 4~6: If the inverter stops and re-starts, it will begin a new cycle and continue running
according to the setting of 13-00.
13-00
1~3 4~6
Output Frequency
time
Output
Frequency
Run
Command
Continue running from
unfinished step
stop runrun
time
Output
Frequency
Run
Command
begin a new cycle
stop runrun
ACC/DEC time follow the setting of 00-09/00-10 or 10-05/10-06 in Auto Run Mode.
Note: Auto _ Run Mode Frequency Command 0 =3-01(Keypad Freq)
Figure 4-31 Single cycle auto run: final step hold
Figure 4-32 AUTO_RUN cycle with interrupt