Chapter 4 Software Index
4-16
09-PID function group
Function
Code No.
Description Range/Code
Factory
Setting
Remarks
09-00 PID Mode Selection
0:Disabled
1:Bias D Control
2:Feedback D Control
3:Bias D Reversed Characteristics Control
4:Feedback D Reversed Characteristics
Control
5:Frequency Command + Bias D Control
6:Frequency Command + Feedback D
Control
7:Frequency Command + Bias D Reversed
Characteristics Control
8:Frequency Command + Feedback D
Reversed Characteristics Control
0
09-01 Feedback Gain coefficient 0.00 ~ 10.00 1.00 *1
09-02 Proportional Gain (%) 0.0 ~ 10.0 1.0 *1
09-03 Integration Time (Seconds) 0.0 ~ 100.0 10.0 *1
09-04 Differentiation Time (Seconds) 0.00 ~ 10.00 0.00 *1
09-05 PID Offset
0: Positive
1: Negative
0 *1
09-06 PID Offset Adjust (%) 0 ~ 109 0 *1
09-07
PID Output Lag Filter Time
(Seconds)
0.0 ~ 2.5 0.0 *1
09-08 Feedback Loss Detection Mode
0: Disabled
1: Enabled - Drive Continues to
Operate After Feedback Loss
2: Enabled - Drive "STOPS"
After Feedback Loss
0
09-09
Feedback Loss Detection Level
(%)
0 ~100 0
09-10
Feedback Loss Detection Delay
Time (Seconds)
0.0 ~ 25.0 1.0
09-11 Integration Limit Value (%) 0 ~ 109 100 *1
09-12
Integration Value Resets to Zero
when Feedback Signal Equals
the Intended Value
0:
Disabled
1: 1 Second
30: 30 Seconds
0 ~ 30
0
09-13
Allowable Integration Error
Margin (Units)
(1 Unit = 1/8192)
0 ~100 0
09-14 Sleep Frequency Level 0.00 ~ 400.00 0.00
09-15 Sleep Function Delay Time 0.0 ~ 25.5 0.0
09-16 Wake up frequency Level 0.00 ~ 400.00 0.00
09-17 Wake up function Delay Time 0.0 ~ 25.5 0.0