Chapter 4 Software Index
4-18
11-Keypad display group
Function
Code No.
Description
Range/Code
Factory
Setting
Remarks
11-00 Display Mode
xxxx0: Disable Motor Current Display
xxxx1: Enable Motor Current Display
xxx0x: Disable Motor Voltage Display
xxx1x: Enable Motor Voltage Display
xx0xx: Disable Bus Voltage Display
xx1xx: Enable Bus Voltage Display
x0xxx: Disable temperature Display
x1xxx: Enable temperature Display
0xxxx: Disable PID feedback Display
1xxxx: Enable PID feedback Display
00000 *1
11-01 Custom Units (Line Speed) Value 0~65535 1800 *1
11-02
Custom Units (Line Speed)
Display Mode
0: Drive Output Frequency is
Displayed
1: Line Speed is Displayed in
Integer (xxxx)
2: Line Speed is Displayed with One Decimal
Place (xxx.x)
3: Line Speed is Displayed with Two Decimal
Places (xx.xx)
4: Line Speed is Displayed with
Three Decimal Places (x.xxx
)
0 *1
11-03 Max PID Feedback Setting 0~999 100 *1
11-04 Min PID Feedback Setting 0~999 0 *1
11-05 PID Feedback Display Mode
0:Displayed in Integer (xxx)
1:Displayed with One Decimal Place (xx.x)
2:Displayed with Two Decimal Places (x.xx)
0 *1
11-06
PID Feedback Display Unit
Setting
0:xxx--
1:xxxpb (
pressure)
2:xxxfl (flow)
0 *1
12-User parameter group
Function
Code No.
Description
Range/Code
Factory
Setting
Remarks
12-00 Drive Horsepower Code ----- *3
12-01 Software Version ----- ----- *3
12-02 Fault Log (Last 3 Faults) ----- *3
12-03
Accumulated Operation Time1
(Hours)
0~23 ----- *3
12-04
Accumulated Operation Time2
(Days)
0~65535 ----- *3
12-05
Accumulated Operation Time
Mode
0: Time Under Power
1: Run Mode Time Only
0 *3
12-06 Reset Drive to Factory Settings
1150: Reset to the 50Hz factory setting
1160: Reset to the 60Hz factory setting
----

Table of Contents