Chapter 4 Software Index
4-21
4.4 Parameter Function Description
Group0- The basic parameters group
00-00:Control Mode 0: V/F mode 1: Vector mode (General Purpose)
To select the appropriate vector control mode or V/F mode according to the load characteristics.
1. If V/F mode is selected, please set parameters, group5 to comply with the load features.
Vector is best suited to control the general load or rapidly-changed torque load.
00-01:Volts/Hz Patterns (V/F) = 0 ~ 18
1.00-01= 0~17, V / F Pattern. (Refer to group5)
2.00-01=18, Flexiable V/F pattern, programmable according to parameters 05-04 ~ 05-09.
00-03: Main Run Command Source Select
=0 : Keypad
=1 : External Run/Stop Control
=2 : Communication
=3 : Expansion card (Reserved)
00-04: Alternative Run Command Source Select
=0 : Keypad
=1 : External Run/Stop Control
=2 : Communication
=3 : Expansion card (Reserved)
1. 00-03/00-04=0, the inverter is controlled by the keypad.
2. 00-03/00-04=1, the inverter is controlled by the external terminals, and the Stop key for emergency
stop is operational. (Refer to 04-02 description)
※Note:00-03/00-04=1, please refer to parameter 04-03, 04-04, 04-06, 04-07 for detailed description in
order to ensure safety of operators and machines.
3. 00-03/00-04=2, the inverter is controlled by Communication.
4. 00-03/00-04=3, the inverter is controlled by expansion card.(Reserved).
5. When 01-00 ~ 01-05 is set 13(Main/Alt Control Signal Select), if the terminal is ON, the inverter is
controlled by parameter 00-03, if the terminal is Off, the inverter is controlled by parameter
00-04.
00-05: Main Frequency Command Source Select
=0 : UP/DOWN of Keypad
=1 : Potentiometer on Keypad
=2 : External AI1 Analog Signal Input
=3 : External Up/Down Frequency Control
=4 : Communication setting Frequency
00-06: Alternative Frequency Command Source Select
=0 : UP/DOWN of Keypad
=1 : Potentiometer on Keypad
=2 : External AI1 Analog Signal Input
=3 : External Up/Down Frequency Control
=4 : Communication setting Frequency
1.Please refer to description of parameter group 01-00 ~ 01-05 (multifunction input terminals) for
the function Up/Down terminal.