Chapter 4 Software Index
4-23
Acc/ Dec time 1
(00-09/0-10)
Acc/ Dec time 2
(10-05/10-06)
JOG Acc/Dec time
(00-13/00-14)
Function
preset value
00-05/00-06
determines the
output frequency
00-05/00-06
determines the
output frequency
Run at 00-12
Jog frequency
01-00~01-05=06/07
Jog command
Off Off On
01-00~01-05=08
Toggle Acc/Dec time
Off On Off
00-11 : Operation modes for external terminals
0:Forward/stop-reverse/stop
1:Run/stop-forward/reverse
2:3-wire control mode -run/stop
1.) When operation command 00-03/00-04 = 0 (external terminal), 00-11is valid.
2.) When operation command 00-03/00-04 = 1 (external terminal control), the stop button for
emergency is available. (Refer to04-02 for detail description).
3.) That both forward and reverse commands are ON will be treated as STOP.
300-11 = 2, Control mode is as below:
Figure 4-7 Terminal Board Drive Operation Modes
Figure 4-8 3-Wire start/stop wiring
S1 (RUN)
S2 (STOP)
S3 (FWD/REV)
COM (0V)