Chapter 4 Software Index
4-25
13:Main/sub Control Signal Select
14:Acc/Dec Disabled
15:Up Command
16:Down Command
17:Main/sub Frequency Command Select
18:PID Function Disabled
19: Integration Value Resets to Zero
20:Reset
21: KEB function
22: Auto _ Run Mode
A. The terminals S1- S6 on terminal block (TM2) are multifunction input terminals. The 23 functions
shown above can be set for these terminals.
B. Function Description for 1-00 ~ 05:
1. 01-00~05=0/1(Forward/Reverse/Stop)
As forward command is ON, the inverter runs and stops when the command is OFF. The 1-00
factory setting is forward.
As reverse command is ON, the inverter runs and stops when the command is OFF. The 1-01
factory setting is reverse.
2. 01-00~05=2/3/4/5 (Frequency Command 1/2/4/8 at 3-02/3-03/3-05/3-08)
When External multifunction input terminals are ON, the inverter is operates at the preset speed
and the duration is determined by the time the input is ON. The corresponding preset frequency
will be according to preset value of parameters 3-01 to 3-16 and in relation to the operation of
input terminals 1 to 4. as shown in the table below:
Output frequency
preset value
Multifunction
terminal 4
Preset value =5
Multifunction
terminal 3
Preset value =4
Multifunction
terminal 2
Preset value =3
Multifunction
terminal 1
Preset value =2
3-01 0 0 0 0
3-02 0 0 0 1
3-03 0 0 1 0
3-04 0 0 1 1
3-05 0 1 0 0
3-06 0 1 0 1
3-07 0 1 1 0
3-08 0 1 1 1
3-09 1 0 0 0
3-10 1 0 0 1
3-11 1 0 1 0
3-12 1 0 1 1
3-13 1 1 0 0
3-14 1 1 0 1
3-15 1 1 1 0
3-16 1 1 1 1
3. 01-00~05=6/7(Forward/ Reverse JOG)
When Jog operation, is selected, the inverter operates at the Jog acceleration and deceleration
times. The corresponding jog frequency parameter is shown below:
The priority order of frequency: Jog Speed→Preset Speed→Keypad frequency or
external frequency signal
4. 01-00~05=8 (Acc/Dec time selection)
This input selects the acceleration 1/ deceleration 1 or acceleration 2/ deceleration 2/.