App3
Appendix 3 :S317+ Parameters Description
1、Add parameters and modify Defult values as follows:
Code
Description Range Defult
NOTE
07-05
Electronic Motor Overload
Protection Operation Mode OL1
0: Enable motor Protect by relay
1: Disable motor Protect by relay
0
07-13
OH over heat Protection
( cooling fan control)
0: Auto (Depends on temp.)
1: Operate while in RUN mode
2: Always Run
3: Disabled
2
07-14
Motor overload protection OL3
0:Enable
1:Disable
0
07-15
OL3 Manual reset time
0.0~5.0min
0min
07-14 Description:
OL3 curve is as follows: running at 120% motor rated current 1 min,turning OL3 protection,
running at 150% motor rated current 2 sec,turning OL3 protection, motor stops running.
2、Manual reset but not automatic reset failure indication, modified as follows:
Display
Description reason measures
OL3
Motor overload OL3 protection.
Manual reset time is
determined by 07-15.
1.Excessive load
2.Incorrect settings
for 06-01.
1. Increase the motor capacity.
2. set 06-01.
Current(%)
(motor rated current)
150
2S
120
Time(s)
60S