© 2009 D 527 - 06/09 14 of 28
12 34
1234
tNt 530
530
One Stage Heat /
One Stage Cool / One Fan
Made in
Canada
Mmm YYYY
Lot # 12345
Meets Class B:
Canadian ICES
FCC Part 15
1023-04
tN2
1
tN2
2
Switch Settings:
For instructions see brochure
Use at least 65°C conductors
Setback
Scene
None
Hydronic
ON
Other
Cool Master 1
Off
Off
5
G
4
Y
3
Rc
Relays: 24V (ac) 2A
12 34
1234
Switch Settings:
Setback
Scene
None
Hydronic
ON
Other
Cool Master 1
Off
Off
DIP Switch Settings
Thermostat 530 DIP Switches
These DIP switches are located on the inside of the thermostat cover. They are shipped “On” from the factory, and will not
have to be adjusted for most applications.
The Thermostat 530 operates a single hydronic heating system zone together with a cooling system and fan.
12 34
1234
tNt 530
530
One Stage Heat /
One Stage Cool / One Fan
Made in
Canada
Mmm YYYY
Lot # 12345
Meets Class B:
Canadian ICES
FCC Part 15
1023-04
tN2
1
tN2
2
Switch Settings:
For instructions see brochure
Use at least 65°C conductors
Setback
Scene
None
Hydronic
ON
Other
Cool Master 1
Off
Off
5
G
4
Y
3
Rc
Relays: 24V (ac) 2A
tN2 Manager, Module
or Wiring Center
530 tNt
Cooling Equipment
1 Stage
Cooling
1 Stage
Fan
G Y R
D
X
Fan
Cooling
tN2 tN2
Test
Cooling System
Note:
Cooling connection
can be made from
either the 530 or
a Zone Manager 334
or Zone Expansion
Module 324
OR
Heating System
Reset
Module
Zone
Manager
530
Cooling System
530 Thermostat
Description
Switch Position Action
1
ON
Setback
Thermostat will follow a schedule
device if one is present on the system.
(Can follow Schedules 1 through 4.)
OFF
OFF
Thermostat does not follow a
schedule.
2
ON
Scene
The thermostat responds to Scene
changes (see “Scenes”, Page 20).
OFF
OFF
Thermostat will not respond to
Scenes.
Switch Position Action
3
ON
None
Thermostat is not part of a cooling
group.
OFF
Cool Master
Thermostat joins as a master of Cool
Group number 1.
4
ON
Hydronic
Heat source is hydronic.
OFF
Other
Other heat source (Furnace, Electric).