AFA4000/E VAV Airflow Controller / p.161
Menu item
Option
Instructions
Sensors (cont.)
Personnel (Sensor)
Set the input activation for the personnel
sensor:
Normally Open (N/O) Contact
Normally Closed (N/C) Contact
Disabled
Sash String Type
Set the input activation for the sash
string:
SP1-50
SP-120
Motor Drive
Motor Voltage
Set the motor voltage:
6-24V
Motor Speed Open
Set the motor speed:
30-100%
Motor Speed Closed
Set the motor speed:
30-100%
Clutch Off Delay
Set the delay time:
0.0-1.00sec
Overcurrent Open
Set the overccurent level:
50-3000mA
Overcurrent Close
Set the overccurent level:
50-3000mA
Stall Detect Sensitivity
Set the sensitivity level:
1-6
Stall Detect Delay
Set the delay time:
1-5 Seconds