User Manual CXE85X
59300464 Rev.005
9.12.2013 31(44)
HIHI: High major alarm limit
HI: High minor alarm limit.
LO: Low minor alarm limit
LOLO: Low major alarm limit.
Deadband: Specifies how much the measured value has to be on the "safe"
side of alarm limit before turning off the alarm.
Unit: Unit of the measured parameter.
For each analog parameter, the current value is displayed and the values of all
alarm thresholds. There are four thresholds: HIHI, HI, LO and LOLO. It’s
possible to disable/enable each threshold by uncheck/check the checkbox
associated to the threshold.
Discrete
Each monitored discrete parameter of the unit is displayed in the lower half of
the frame with following information in the list:
Name: Name of the monitored parameter.
Alarm: Alarm status of the parameter: Nominal / Major / Minor. If the alarm is
disabled, but parameter is in alarming state, "Nominal" is shown.
Setting: Alarm severity can be configured to Major, Minor or Disabled.
For each discrete parameter, the current value is displayed; also the current
alarm value associated and the level of the alarm associated.