www.temcoline.com
DIGITAL PID CONTROLLER
17
5. Ratings and Specifications
T50 SERIESModel
Power Supply
Power Consumption
Dispaly Accuracy
Control
Output
Alarm
Output
ALARM 1, 2
HBA common
(C.T)
Relay
Voltage
(S.S.R)
Current
(S.C.R)
Input Impedance
Input Sampling Period
Control Method
Multi SV Input(D.I)
Retransmission
Output
Communication
Output
Ambient Temperature
and Humidity
Weight
(Bracket, Accessories included)
Input Type
5VA (Max.)
±0.3% of FS +1 Digit
50~250ms (variable according to SG-PID algorithm)
DC15V 25mA (Built-in short protection circuit)
Voltage pulse (time proportional PID output)
4~20mA DC, load impedance ≤ 600Ω(continuous PID output)
Super 2 degree-of-freedom PID (SG-PID algorithm),
S-Fuzzy, Auto-Tuning
ON: ≤ 1KΩ, OFF: ≥ 100KΩ(external control SV1, 2, 3)
TC: K, J, T, E, R, B, S, L, N, U, C(W5), D(W3)
Platinum RTD: KPt100(KS), JPt100(JIS), Pt100(DIN)
Current input(A): 4~20mA DC
Voltage input(V): 1~5V DC, -10~20mV DC, 0~100mV DC
2 wires RS485 totally independent isolation structure
Max. speed: 19,200bps/ Max. connect no. 99 devices (32
devices recommended) Support protocol: PC-Link, TL-
Link, Modbus-ASCII, Modbus-RTU
Rating 100~240V AC 50~60Hz (voltage operating range: 85~265V AC)
※ Option: Rating 24V AC or DC (operating voltage range 20~28V DC)
Current input(250Ω), Voltage input(including TC) 1MΩ min.
(RTD line resistance: ≤ 10Ω, when 3-line resistance are
the same)
1c 250V AC, 3A(resistance load) electric lifespan ≥ 100,000 min.
(time proportional PID output or ON/OFF output)
4~20mA DC, load impedance ≤ 600Ω resolution 1/4,600
PV(process value), SV(set value), MV(manipulated variable [%]),
SPS(sensor module power supply)
1a 250V AC 3A (Resistive load)
HBA: 0.1 ~ 38.0 A AC (Resolution 0.1A)
-10~50℃/ relative humidity 25~85% RH
(but with neither condensation nor freezing)
T52, T53, T57: 230g T54: 140g T59: 320g
※ + 30g, if options are added