DIGITAL PID CONTROLLER
28
⑩ Disiable function of reset on front ( )
Set whether to use latch function ON or OFF when using alarm function.
⑪ Setting the indicator mode
This function is for use only for monitoring without using the control
function. When this function is set, all control related functions are
not displayed and all parameters and user interface are automatically
optimized as monitoring dedicated devices.
※ In the indicator mode, only 4. HBA setting group / 5. ALM setting group / 6. TRS setting
group / 7. COM setting group / 9. IN setting group and special function setting menu can
be set.
※ In the HBA setup menu, the ammeter function and the overcurrent (HOC) alarm and the
HBA alarm are used as the current lower limit alarm function.
※ SV window can be used as a general ammeter. Depending on the alarm and settings.
front reset ON/OFF
Current detector(CT 800: 1)
TC8L or CTL-6-S
T54-C2x, C5x (HBA option model)
ⓐ SV: set temperature of alam ⓑ SV: Heater or other current