Type Wire Gauge Wire Strip Length
1 Ground 4-6 mm
2
(10-12
AWG), 60 °C
8 to 12 mm
2 High voltage (+/-) 4-6 mm
2
(10-12
AWG), 60 °C
12 to 16 mm
3 Enable line 0.5-1 mm
2
(18-22
AWG), 60 °C
7 to 9 mm
4 Logic (+/-) 0.5-1 mm
2
(18-22
AWG), 60 °C
7 to 9 mm
5 Communications 0.5-1 mm
2
(18-22
AWG), 60 °C
7 to 9 mm
6 Thermal power (+/-) 1.5 mm
2
(16
AWG), 60 °C
7 to 9 mm
7 Primary connector (J7)
8 Output connector for multiple units (J6)
9 Enable button (disables power when splash cover is o)