TSC 80e TRANSFER SWITCH CONTROLLER
PM091 Rev 0 09/01/21 Thomson Technology
23
3.6.1.1.SOFTWARE VERSION
The LCD screen displays the current version number of TSC 80e software
installed in the controller.
3.6.1.2.SYSTEM TIME CLOCK
The LCD screen displays the current date and time, based on what has been
programmed to the TSC 80e controller.
3.6.1.3.GENERATOR VOLTAGE/FREQUENCY
The LCD screen displays the current generator voltage (3 phase or single
phase, line– to – line or line to neutral voltages) and frequency.
3.6.1.4.UTILITY VOLTAGE/FREQUENCY
The LCD screen displays the current utility voltage (3 phase or single phase,
line– to – line or line to neutral voltages) and frequency.
3.6.1.5.SYSTEM CONFIGURATION
The LCD screen displays the current system configuration setup in the TSC
80e program software:
VOLTAGE (120, 128, 208, 220, 230, 240, 380, 400, 440, 460, 480, 575,
600V). Note: voltage setting is dependent on type of voltage sensing
used on the ATS (i.e. with or without potential transformers). Refer to
section 5.4.5.
FREQUENCY (50, 60Hz)
PHASES (single or 3 phase)
3.6.1.6.GENERATOR UNDER VOLTAGE SETPOINT
The LCD screen displays the programmed generator under voltage sensor
setpoint value and the associated dropout % in the TSC 80e controller
(percentage is based on nominal voltage level selected in System
Configuration).
3.6.1.7.GENERATOR UNDER FREQUENCY SETPOINT
The LCD screen displays the programmed generator under frequency sensor
setpoint value and the associated dropout % in the TSC 80e controller
(percentage is based on nominal frequency level selected in System
Configuration).