TSC 80e TRANSFER SWITCH CONTROLLER
PM091 Rev 0 09/01/21 Thomson Technology
34
• Gen Test Start
• Load on Gen
• Gen Test Stop
NOTE:
A Master Password is required to change this
parameter
4.6.2. SYSTEM DATE & TIME
This sub-menu item is used to set the controllers real time clock. This clock is utilized
for operation of the programmable plant exercise function and data logging time/date
stamping. The controllers clock’s time & date setting has a battery back-up feature,
which will maintain the clocks setting during normal utility power interruptions. The
battery back-up feature has a reserve capacity to allow the clock time to be saved for
up to 100 hours following loss of control power to the controller. The time clock also
has a daylight saving feature as described in Section #4.6.5.12
The following sub-menus are located within this section:
4.6.2.1.Year
4.6.2.2.Month
4.6.2.3.Date
4.6.2.4.Hours
4.6.2.5.Minutes
4.6.2.6.Seconds
Refer to Section 4.2 for programming change procedure.
4.6.3. AUTO EXERCISE TIMER
The TSC 80e controller has a built-in programmable exercise timer, which allows up to
a 4 week (28 day), exercise time period. The timer is fully programmable for, day of
week, time of day, duration of the test and type of test mode (i.e. On or Off Load). The
exercise timer utilizes the TSC 80e’s internal real-time-clock clock for referencing all
timing functions. The time clock has a 500-hour power reserve feature to retain correct
time settings during short duration utility power failures. NOTE: During any On Load