TSC 80e TRANSFER SWITCH CONTROLLER
PM091 Rev 0 09/01/21 Thomson Technology
50
Normally Closed- TB2 –15
Normally Open- TB2 –16
Note: The ATS will be factory wired for programmable output #4 as Load on
Generator. If a different function is programmed, the ATS relay installed will
need to be re-assigned accordingly.
4.6.10.5.Programmable Output #5
Programmable output #5 corresponds to the following output relay contacts:
Common- TB2 –11
Normally Closed- TB2 –12
Normally Open- TB2 –13
Note: Factory default setting for programmable output #5 is Load on Utility. If
a different function is programmed, the ATS relay installed will need to be re-
assigned accordingly.
4.6.11.SYSTEM STATISTICS
4.6.11.1.Xfer Total
Displays Total Number of Transfers
4.6.11.2.Monitoring Time
Displays Total Number of Hours the Controller is energized
4.6.11.3.Load on Gen
Displays Total Number of Hours Load is on Generator
4.6.11.4.Load on Utility
Displays Total Number of Hours Load is on Utility
4.6.11.5. Xfers Util Fault
Displays Total Number of Transfers due to a utility failure

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the THOMSON TSC 80E - V2.1 and is the answer not in the manual?

THOMSON TSC 80E - V2.1 Specifications

General IconGeneral
BrandTHOMSON
ModelTSC 80E - V2.1
CategoryController
LanguageEnglish

Related product manuals