EasyManua.ls Logo

Thytronic NC020 - Phase Overcurrent 50;51 - very Inverse Time Curve (ANSI;IEEE Type VI)

Thytronic NC020
86 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
APPENDIX
77
NC020 - Manual - 05 - 2022
Phase overcurrent 50/51 - Very inverse time curve (ANSI/IEEE type VI)
F_51-ANSIVI-Char.ai
1.1
2 3 4 5 6 7 8 9 10 20
I
/I>>
inv
I
RMS
/I>
inv
0.01
0.1
1
10
100
1000
10000
t [s]
10 s
60 s
t>
inv
t>>
inv
5 s
1 s
0.5 s
0.2 s
0.1 s
0.02 s
t =
t>
inv
·
[(I
RMS
/I>
inv
)
2
-1]
3.922
+ 0.092
t =
t>>
inv
·
[(I
/I>>
inv
)
2
-1]
3.922
+ 0.092
Note: match of operating and setting time takes place when I
RMS
/I>
inv
= 2.306

Table of Contents

Related product manuals