Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
Note: NO/NC = Normally Opened/Normally Closed contact. NO/NC selection numbers are used when
making system changes via communications.
102 103
Commercial Power/ASD Switching — Initiates the ASD-to-Commercial Power switching
function. See F354 for additional information on this feature.
104 105
Frequency Command Priority Switching — Toggles frequency control to and from the set-
tings of F004 and F207.
106 107
V/I Terminal Priority — Assigns Speed control to the V/I Terminal and overrides the F004
setting.
108 109
Command Terminal Board Priority — Assigns Command control to the Terminal Board and
overrides the F003 setting.
110 111
Parameter Edit Enable — Allows for the override of the lock out parameter setting (F700)
allowing for parameter editing (SELECTION NOT USED WITH THE Q9 Plus ASD).
122 123
Fastest Deceleration Command — Using dynamic braking (if enabled and supported), stops
the motor at the fastest rate allowed by the load.
124 125
Preliminary Excitation — Applies an excitation current to the motor (holds shaft stationary)
for the duration of the activation.
136 137
Start-Stop HOA — Activates the Auto Start-Stop operating mode in accordance with the set-
tings of F385.
138 139
Low Suction/No Flow Protection — Will not allow the ASD to start if activated, or terminates
the ASD output upon activation (if running) in the event of the loss of feed water or a closed
output valve at the pump output.
140 141
Sealing Water — Once an adequate water supply is detected at the pump seal via a reed
switch, activation enables the ASD for normal operations.
142 143
Virtual Linear Pump Enable/Disable Switch — Activation enables the Virtual Linear Pump
function for normal operation. The Virtual Linear Pump function is disabled when the terminal
is not active.
144 145 TBA ON Float — Activation runs the ASD at the setting of F390.
146 147
TBA OFF Float — Activation has a dual function:
1) Changes the operating mode from Process Hold to Direct.
2) Turns off the ASD.
148 149 TBA Trigger Float — Activation changes the operating mode from Process Hold to Direct.
150 151
TBA Warning Float — This input is typically connected to a float switch that, when activated,
annunciates that the fluid level is now critical. The discrete output terminals OUT1 and/or
OUT2 may be associated with the activation (set OUT1/OUT2 to TBA Alarm Float to activate
an auxiliary system — i.e., aux pump, relief valve, audible/visual alarm, etc.).
152 153
TBA Local-Off-Auto — Activation enables Time-Based Alternation operation. Operates in
conjunction with the setting of F417.
154 155 V/Hz Rate Switching — This function is not used with the Q9 Plus ASD.
156 157
Manual Boost Switching — Activation applies the torque boost setting of F016 and F172 to
motor profiles 1 and 2, respectively, for the duration of the activation.
Table 9. Discrete Input Terminal Assignment Selections and Descriptions. (Cont)
Sel. No.
Terminal Selection Descriptions
NO NC
Sealing
Water