IF08CZ10 April, 2019 - 33 -
INTERFACE (cont’d)
Digital Input Descriptions **
Name Description
JOG0 Jog speed reference selection bit 0
JOG1 Jog speed reference selection bit 1
JOG2 Jog speed reference selection bit 2
JOG3 Jog speed reference selection bit 3
LATCH_PG_POS PG counter latch command Latch at rising and falling edges of this signal.
LB Load balance between stands Load balance control when 1
M_FN_ Motor fan stopped
MP_BE_TM_H1_ BearingTempHigh1 0:Tmperature High
MP_BE_TM_H2_ BearingTempHigh2 0:Temperature High
MP_BE_TM_H3_ BearingTempHigh3 0:Temperature High
MP_BH_RL_A_ BuchholzRelayAlarm 0:Alarm
MP_BH_RL_TR_ BuchholzRelayTrip 0:Trip
MP_BR01_CL MotorBreaker01Closed 1:Closed
MP_BR02_CL MotorBreaker02Closed 1:Closed
MP_BR03_CL MotorBreaker03Closed 1:Closed
MP_BR04_CL MotorBreaker04Closed 1:Closed
MP_BR05_CL MotorBreaker05Closed 1:Closed
MP_BR06_CL MotorBreaker06Closed 1:Closed
MP_BR07_CL MotorBreaker07Closed 1:Closed
MP_BR08_CL MotorBreaker08Closed 1:Closed
MP_BR09_CL MotorBreaker09Closed 1:Closed
MP_BR10_CL MotorBreaker10Closed 1:Closed
MP_CF_IL_ CoolingFan I/L SW 0:Interlocked
MP_CF1_MCC_F_ CoolingFan1MCC Fault 0:Fault
MP_CF1_MR CoolingFan1MotorRun 1:Running
MP_CF2_MCC_F_ CoolingFan2MCC Fault 0:Fault
MP_CF2_MR CoolingFan2MotorRun 1:Running
MP_CW_TM_H1_ CoolingWaterTempHi1 0:Temperature High
MP_CWF_L1_ CoolingWaterFlowLow1 0:Flow Low
MP_GP_RL_TR_ SuddenGasPressRyTrip 0:Trip
MP_OL_LVL_A_ OilLevelAlarm 0:Alarm
MP_OL_LVL_TR_ OilLevelTrip 0:Trip
MP_OL_P_IL_ OilLubPump I/L SW 0:Interlocked
MP_OL_TM_A_ OilTemperatureAlarm 0:Alarm
MP_OL_TM_TR_ OilTemperatureTrip 0:Trip
MP_OLU_HFD_ OilLubricationUniHFD 0:Fault
MP_OLU_HPL_N OilLubUHiPressLineN 1:Normal
MP_OLU_LFD_ OilLubricationUniLFD 0:Alarm