- 28
QSTOP Quick stop command 1:Quick stop, 0:Normal stop
R-TEN Reverse tension command 1:Reverse tension control on,
0:Forward tension control on
SEL_DI Start/Stop/Reference/direction select 0:Use EXT0,START0,STOP0,SP_REF_AIN1,DIR0_DI
1:Use EXT1,START1,STOP1,SP_REF_AIN2,DIR1_DI
SPA0 Spare 0 Spare 0 (For future use)
SPA1 Spare 1 Spare 1
SPA2 Spare 2 Spare 2
SPA3 Spare 3 Spare 3
SPA4 Spare 4 Spare 4
SP_UP_DI Raise speed reference 0:no change, 1:Raise speed reference
(Operates only when keypad is in remote mode. Use in
conjunction with CR_RATE_MRH)
SP_DN_DI Lower speed reference 0:No change, 1:Lower speed reference
(Operates only when keypad is in remote mode. Use in
conjunction with CR_RATE_MRH)
START0_DI Start command for three wire control 0
START1_DI Start command for three wire control 1
0:No start, 1:Start
(Must be momentary. Refer to SEL_DI)
STOP0_DI Stop command for three wire control 0
STOP1_DI Stop command for three wire control 1
0:No stop, 1:Stop
(Refer to SEL_DI)
ST_CLUTCH Torque control selection
1:Tension control,
0: Speed control (when torque control is selected)
UVS Operation interlock 1:Interlock released, 0: Interlocked
3S 3
rd
jogging speed command
2S 2
nd
logging speed command
(3S, 2S)=(0,0) :Jog speed 1 used
(3S, 2S)=(0,1) :Jog speed 2 used
(3S, 2S)=(1,0) :Jog speed 3 used
(3S, 2S)=(1,1) :No jog speed used
ā**ā The function of many operation signals can be reversed via settings for SGN_DI1-8 or SGN_DI_EX4 if needed.