TE2 Series Digital Solid State Soft Starter User Manual       51 | Page 
 
F050 =  Minimum Time Between Starts Lockout 
Factory Setting = 0 (Disabled) 
Range = 1 - 60 minutes, or 0 (Disabled) 
When F050 is set to 1 through 60, the motor cannot be 
restarted within the time specified after the first start. Time 
between starts is calculated from the time of the first start 
command to the next regardless of run time or off time. 
 
Example: 
If F050 = 15, motor will not be allowed to re-start within 15 
minutes of the first start. 
 
This function is useful as a “Short-Cycle Timer” to prevent 
excessive motor wear when automatic demand control may 
occasionally cycle on and off too quickly. e.g. compressors or 
sump pumps. 
 
5.6.9.a Control Power Trip (F051) 
 
F051 =  nCP Trip 
Factory Setting = 0 (Disabled) 
Range = 0 (Disabled), 1 (Enabled) 
When F051 is set to 1, TE2 trips when control power is lost.  
 
5.6.9.b Auto-Reset Programming (F052 - F054) 
The TE2 Series can be programmed to automatically attempt a 
reset based on the selected “Auto-Reset” faults (F52), provided a 
Start Command is present (see Section 4.2), and no fault condition 
is active.  Function F52 selects the “Auto-Reset” faults and function 
F53 sets the number of reset attempts. If F053 is set to 0 (default 
setting), the TE2 Series auto-reset function is disabled.  
  Note: 
When using 3-wire control:  
For safety reasons, the TE2 Series will not attempt restarting 
unless the Start Command is reinitiated and maintained during a 
restart attempt.