TE2 Series Digital Solid State Soft Starter User Manual 52 | Page
F052 = Auto-Reset Selected Faults
Factory Setting = 4 (Phase Loss)
Range = 1 - 17, or 0 (Disabled)
If F052 = 1 through 17, the TE2 Series will attempt to restart
after the fault(s) coded in the following table. Only one selection
can be entered.
F052
Setting
Fault Condition
Description
Display
Readout
Reference
F052
Setting
Fault Condition
Description
Display
Readout
Reference
0 Auto Reset Disabled --- 10
Under Voltage UE
1 Over Temperature Trip
OT
11 Power Factor PF
2
Over Current (Shear
Pin) Trip
OC
12
PoweR (KW) PR
3 Under Current Trip
UC
13
Any fault #1-3 above
4 Phase Loss Trip
PL
14 Any fault #4-6 above
5 Current Unbalance Trip
IB
15 Any fault except #7
6 Ground Fault Trip
GF
16
Any fault except #6 & #7
7 Short Circuit Trip
SC
17 Any fault
8 Voltage Imbalance EI
Note 1: UC, OC or UB require operation to resume before the fault can be detected.
Note 2: Cycling and / or restoration of control power will reset all of the above faults.
Note 3: Overload Trip reset function is programmed only in F005. See Section 3 for details
Note 4: Reset attempts with a fault condition present will cause a new fault. This will be logged into the fault history (F085 - F093) and may
overwrite previous fault records.
Table 5.6.8.b: Faults Selected for Auto-Restart
F053 = Auto-Restart Attempts
Factory Setting = 0 (Disabled)
Range = 1 - 10 Attempts, or 0 (Disabled)
If F053 = 1 through 10, the TE2 Series will attempt to restart if
the Start Command is present for this number of times. If set to
Zero, the starter will NOT attempt to reset automatically.