TE2 Series Digital Solid State Soft Starter User Manual       52 | Page 
 
F052 =  Auto-Reset Selected Faults 
Factory Setting = 4 (Phase Loss) 
Range = 1 - 17, or 0 (Disabled) 
If F052 = 1 through 17, the TE2 Series will attempt to restart 
after the fault(s) coded in the following table. Only one selection 
can be entered. 
F052 
Setting 
Fault Condition 
Description 
Display 
Readout  
Reference 
F052 
Setting 
Fault Condition 
Description 
Display 
Readout  
Reference 
0  Auto Reset Disabled  ---  10 
Under Voltage  UE 
1  Over Temperature Trip 
OT 
11  Power Factor  PF 
2 
Over Current (Shear 
Pin) Trip 
OC 
12 
PoweR (KW)  PR 
3  Under Current Trip 
UC 
13 
Any fault #1-3 above 
 
4  Phase Loss Trip 
PL 
14  Any fault #4-6 above 
 
5  Current Unbalance Trip 
IB 
15  Any fault except #7 
 
6  Ground Fault Trip 
GF 
16 
Any fault except #6 & #7 
 
7  Short Circuit Trip 
SC 
17  Any fault 
 
8  Voltage Imbalance  EI       
Note 1: UC, OC or UB require operation to resume before the fault can be detected. 
Note 2: Cycling and / or restoration of control power will reset all of the above faults.  
Note 3: Overload Trip reset function is programmed only in F005. See Section 3 for details 
Note 4: Reset attempts with a fault condition present will cause a new fault. This will be logged into the fault history (F085 - F093) and may 
overwrite previous fault records. 
Table 5.6.8.b:  Faults Selected for Auto-Restart  
     
 
F053 =  Auto-Restart Attempts 
Factory Setting = 0 (Disabled) 
Range = 1 - 10 Attempts, or 0 (Disabled) 
If F053 = 1 through 10, the TE2 Series will attempt to restart if 
the Start Command is present for this number of times. If set to 
Zero, the starter will NOT attempt to reset automatically.