TE2 Series Digital Solid State Soft Starter User Manual 68 | Page
Display Message Description
Fault Display
Code
Readout
Fault Number
Code used in
History,
F085, F088
and F091
LED
Indicator
No Full Load Amps entered into F001
nFL
A
Over Current During Accel
oc
A
1
Over
Current
Over Current During Constant Speed
occ
2
Over Current During Decel (or Stop)
ocd
3
Phase Loss During Accel
PL
A
4
Phase Loss
Phase Loss During Constant Speed
PLc
5
Phase Loss During Decel (or Stop)
PLd
6
Line Voltage loss (no 3 phase prior to start)
n3Ph
6
Over Temperature During Accel
ot
A
7
Over Temp
Over Temperature During Constant Speed
otc
8
Over Temperature During Decel (or Stop)
otd
9
Over Load During Accel
oL
A
10
Overload
Over Load During Constant Speed
oLc
11
Over Load During Decel (or Stop)
oLd
12
Shorted SCR During Accel
SS
A
13
Shorted
SCR or
no load
Shorted SCR During Constant Speed
SSc
14
Shorted SCR During Decel (or Stop)
SSd
15
Shunt Trip During Accel
St
16
Shunt Trip
Shunt Trip During Constant Speed
St
17
Shunt Trip During Decel (or Stop)
St
18
Im-Balance Current During Accel
Ib
A
19
---
Im-Balance Current During Constant Speed
Ibc
20
Im-Balance Current During Decel (or Stop)
Ibd
21
Under Current During Accel
Uc
A
22
---
Under Current During Constant Speed
Ucc
23
Under Current During Decel (or Stop)
Ucd
24
Short Circuit During Accel
Sc
A
25
Over
Current
Short Circuit During Constant Speed
Scc
26
Short Circuit During Decel (or Stop)
Scd
27
Ground Fault During Accel
GF
A
28
---
Ground Fault During Constant Speed
GFc
29
Ground Fault During Decel (or Stop)
GFd
30
Bypass Discrepancy Fault During Accel
bP
A
31
---
Bypass Discrepancy Fault During Constant Speed
bPc
32
Bypass Discrepancy Fault During Decel (or Stop)
bPd
33
External Lockout Fault During Accel
Lc
A
34
Overload
External Lockout Fault During Constant Speed
Lcc
35
External Lockout Fault During Decel (or Stop)
Lcd
36
Phase Rotation Fault During Accel
rot
A
37
Phase Rotation Fault During Constant Speed
rotc
38 ---
Phase Rotation Fault During Decel (or Stop)
rotd
39
Table 7.1: Message Fault code List

Table of Contents