TE2 Series Digital Solid State Soft Starter User Manual 86 | Page
Fn # Group Function Description Adjustment / Display Range
Setting
Increments
Factory
Setting
Setting
F29
Line Voltage
Voltage Input 200 - 690 Volt 1 480
F030 Voltage Imbalance Trip % 0, 1 - 30% [0=Disabled] 1(%) 0
F031 Voltage Imbalance Trip Delay 1 - 20 seconds 1 10
F032 Over Voltage Trip % 0, 1 - 10% [0=Disabled] 1(%) 0
F033 Over Voltage Trip Delay 1 - 20 seconds 1 10
F034 Under Voltage Trip on Start % 0, 1 - 20% [0=Disabled] 1(%) 0
F035 UV Trip on Start Delay 1 - 180 seconds 1 10
F036 Under Voltage Trip on Run % 0, 1 - 20% [0=Disabled] 1(%) 0
F037 UV Trip Delay during Run 1 - 20 seconds 1 2
F038 Shorted SCR and Trip Delay 0, 1-10 seconds [0=Disabled] 1 second 1 second
F039 Shunt Trip Delay 0, 1-10 seconds [0=Disabled] 1 second 1 second
Fn # Group Function Description Adjustment / Display Range
Setting
Increments
Factory
Setting
Setting
F040
Phase Current
Current Imbalance Trip
0 = Disabled, or
5 - 30% imbalance
1%
0
Disabled
F041 Current Imbalance Trip Delay 1 - 20 seconds 1 second
2
seconds
F042 Over Current Trip
0 = Disabled, or
100 - 300% of motor FLA
1%
0
Disabled
F043 Over Current Trip Delay 1 - 20 seconds 1 second 1 second
F044 Under Current Trip
0 = Disabled, or
10 - 90% of motor FLA
1%
0
Disabled
F045 Under Current Trip Delay 1 - 60 seconds 1 second
2
seconds
F046 Ground Fault Trip
0 = Disabled, or
5 - 90% of CT ratio from Fn 74
1%
0
Disabled
F047 Ground Fault Trip Delay 1 - 60 seconds 1 second
2
seconds