E6581697
F-30
6
6.12 Preset-speed frequencies
f287 to f294 : Preset-speed frequency 8 to 15
Refer to section 3.6 for details.
6.13 Bumpless operation
f295 : Bumpless operation selection
f732 : Local/remote key prohibition of extension panel
Function
When switching from Remote mode to Local mode, the status of start and stop, and operating
frequency at Remote mode are moved to Local mode.
By contraries, when switching from Local mode to Remote mode, they are not moved to Remote
mode.
[Parameter setting]
Title Function Adjustment range Default setting
f295
Bumpless operation selection
0: Disabled
1: Enabled
0
f732
Local/remote key prohibition of
extension panel
0: Permitted
1: Prohibited
1
, key is assigned to Local/remote function.
Set parameter
f750 (EASY key function selection) = 2 (Local / remote key).
EASY lamp is lighting, during selecting local mode.
, LOC/REM key of extension panel option (RKP007Z) can be used.
In case, set parameter
f732 (Local/remote key prohibition of extension panel) = 0 (Permitted).