E6581697
F-41
6
• When the motor is started again after the synchronized deceleration function stop, turn off the power failure
synchronized signal.
• In case of using the synchronized deceleration function, confirm not to work overvoltage stall prevention function
during deceleration.
An example of setting when f302=4
Synchronized deceleration if a power failure synchronized signal is impressed or if a power failure occurs, or
synchronized acceleration if the power failure synchronized signal is canceled.
Motor speed
Time
Synchronized
acceleration/dece
leration signal
(S1 terminal)

Inverter 1

Inverter 2
ON


Input voltage
*1
Power failure
synchronized
signal
ON
OFF