[Parameter setting]
Title Function Adjustment range Default setting
f702
Frequency free unit display
magnification
0.00: Disabled (display of frequency)
0.01-200.0 (times)
0.00
f703
Frequency free unit coverage
selection
0: All frequencies display
1: PID frequencies display
0
f705
Inclination characteristic of free unit
display
0: Negative inclination (downward
slope)
1: Positive inclination (upward slope)
1
f706
Free unit display bias 0.00-
fh (Hz) 0.00
* The
f702 converts the following parameter settings:
In case of
f703=0
Free unit Frequency monitor display Operation frequency command, Operation
frequency, PID feedback, Frequency command
value After correction, Operation frequency
command at trip
Frequency-related parameters
fc, fh, ul, ll, sr1 sr7,
f100, f101, f102, f167, f190,
f192, f194, f196, f198, f202,
f204, f211, f213, f217, f219
f240, f241, f242, f250, f260,
f265, f267, f268, f270 to f275,
f287 f294, f330, f331, f346,
f350, f367, f368, f383,
f390 to f393, f505, f513, f649,
f812, f814, a923 to a927
In case of
f703=1
Free unit PID control -related parameters fpid, f367, f368
Note) The unit of the Base frequency 1 and 2 are always Hz.
■ An example of setting when fh is 80 and f702 is 10.00
f705=1, f706=0.00 f705=1, f706=20.00