E6581697
J-2
10
ï‚¢ Selection of wiring devices
Input current (A)
Molded case circuit breaker (MCCB)
Earth leakage circuit breaker (ELCB)
Magnetic contactor
(MC) (Note 1 to 4)
Without reactor with ACL Without reactor with ACL
Voltage
class
A
pplicable
motor
(kW)
Without
reactor
With ACL
Rated
current
(A)
MCCB type
(ELCB type)
Rated
current
(A)
MCCB type
(ELCB type)
Rated
current
(A)
Model
Rated
current
(A)
Model
0.2 3.4 2.4 5 5 20 20
0.4 6.0 4.4 10 10 20 20
0.75 10.1 8.1 15 10 20
CA13
20
1.5 17.6 15.3 30 20 32 20
CA13
1 phase
240V
class
2.2 23.9 21.3 30
NJ30E
(NJV30E)
30
NJ30E
(NJV30E)
32
CA20
32 CA20
0.4 2.1 1.5 5 5 20 20
0.75 3.6 2.6 5 5 20 20
1.5 6.5 4.7 10 10 20 20
2.2 8.7 6.4 15 10 20 20
4.0 13.7 10.3 20 15 20
CA13
20
5.5 20.7 14.0 30 20 32 20
CA13
7.5 26.5 18.1 30
NJ30E
(NJV30E)
30
NJ30E
(NJV30E)
32
CA20
32
11 36.6 24.1 50
NJ50EB
(NJV50EB)
40 50 CA25 32
CA20
15 47.3 36.6 60 50
NJ50EB
(NJV50EB)
60 CA35 50 CA25
3 phase
500V
class
Note 6)
18.5 52.6 44.0 75
NJ100FB
(NJV100FB)
60
NJ100EB
(NJV100EB)
80 CA50 60 CA35
The recommended molded case circuit breaker (MCCB) must be connected to primary side of each inverter to
protect the wiring system.
Note 1: Models made by Toshiba Industrial Products Sales Corporation are shown.
Note 2: Be sure to attach a surge killer to the exciting coil of the relay and the magnetic contactor.
Note 3: When using the auxiliary contacts 2a of the magnetic contactor MC for the control circuit, connect the
contacts 2a in parallel to increase reliability.
Note 4: When a motor is driven by commercial power supply using commercial power supply / inverter switching
circuit, use a magnetic contactor appropriated AC-3 class the motor rated current.
Note 5: Select an MCCB with a current breaking rating appropriate to the capacity of the power supply, because
short-circuit currents vary greatly depending on the capacity of the power supply and the condition of the
wiring system. The MCCB, MC and ELCB in this table were selected, on the assumption that a power
supply with a normal capacity would be used.
Note 6: For the operation and control circuits, regulate the voltage at 200V to 240V with a step-down transformer
for 500V class.
Note 7: In case of aul=2 setting, be sure to select the wiring device for 1 rating up motor.
Note 8: Regarding influence of leakage current, refer to section 1.4.3.

Table of Contents

Other manuals for Toshiba TOSVERT VF-MB1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-MB1 and is the answer not in the manual?

Toshiba TOSVERT VF-MB1 Specifications

General IconGeneral
BrandToshiba
ModelTOSVERT VF-MB1
CategoryInverter
LanguageEnglish

Related product manuals