E6581697
K-5
11
11.3 Extended parameters
Input/output parameters 1
Title
Communication
No.
Function Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
0100 Low-speed signal
output frequency
Hz 0.1/0.01 0.0- 0.0 6.1.1
0101 Speed reach
setting frequency
Hz 0.1/0.01 0.0- 0.0 6.1.3
0102 Speed reach
detection band
Hz 0.1/0.01 0.0- 2.5 6.1.2
6.1.3
0104 Always active
function selection 1
- -
0-153 *6 0 (No
function)
6.3.1
0105 Priority selection
(Both F and R are
ON)
- -
0: Reverse
1: Deceleration Stop
1 6.2.1
0107 Analog input
terminal selection
(VIB)
- -
0: 0-+10V
1: -10-+10V
0 6.2.2
6.6.2
7.3
0108 Always active
function selection 2
-
-
0-153 *6 0 (No
function)
6.3.1
0: Analog input for communications
VIB - analog input
1: VIA - analog input
VIB - contact input (Sink)
2: VIA - analog input
VIB - contact input (Source)
3: VIA - contact input (Sink)
VIB - contact input (Sink)
0109 Analog/logic input
selection
(VIA/VIB)
- -
4: VIA - contact input (Source)
VIB - contact input (Source)
0 6.2.3
6.3.2
6.6.2
7.2.1
7.3
0110 Always active
function selection 3
- - 0-153 *6 6
(ST)
6.3.1
0111 Input terminal
selection 1A (F)
- - 2
(F)
0112 Input terminal
selection 2A (R)
- - 4
(R)
0113 Input terminal
selection 3A (RES)
- - 8
(RES)
0114 Input terminal
selection 4A (S1)
- - 10
(SS1)
0115 Input terminal
selection 5 (S2)
- - 12
(SS2)
6.3.2
7.2.1
0116 Input terminal
selection 6 (S3)
- -
0-203 *6
14
(SS3)
0117 Input terminal
selection 7 (VIB)
- - 16
(SS4)
6.3.2
7.2.1
0118 Input terminal
selection 8 (VIA)
- -
8-55 *6
24
(AD2)
*6: Refer to section 11.6 for details about input terminal function.