E6581697
M-3
13
(Continued)
Error code Failure code Problem Possible causes Remedies
The cooling fan does not rotate.
The fan requires replacement if it does
not rotate during operation.
The ambient temperature is too high. Restart the operation by resetting the
inverter after it has cooled down enough.
The vent is blocked up. Secure sufficient space around the inverter.

0010 Overheat
A heat generating device is installed close
to the inverter.
Do not place any heat generating device
near the inverter.

002E
Thermal trip stop
command from
external device
A thermal trip command (input terminal
function:  or ) is issued by an
external control device.
The motor is overheated, so check
whether the current flowing into the motor
exceeds the rated current.

0011 Emergency stop
During automatic operation or remote
operation, a stop command is entered
from the operation panel or a remote
input device.
Reset the inverter.
If the emergency stop signal is input,
reset after releasing this signal.

0012 EEPROM fault 1
A data writing error occurs. Turn off the inverter, then turn it again. If it
does not recover from the error, contact
your Toshiba distributor.

0013 EEPROM fault 2
Power supply is cut off during 
operation and data writing is aborted.
The error occurred when various data
was written.
Turn the power off temporarily and turn it
back on, and then try  operation
again.
Write the data again. Contact your
Toshiba distributor when it happening
frequently.

0014 EEPROM fault 3
A data reading error occurred. Turn off the inverter, then turn it again. If it
does not recover from the error, contact
your Toshiba distributor.

0015 Main unit RAM fault
The control RAM is defective. Contact your Toshiba distributor.

0016 Main unit ROM fault
The control ROM is defective. Contact your Toshiba distributor.

0017 CPU fault 1
The control CPU is defective. Contact your Toshiba distributor.

0018 Communication error
The communication was broken off. Check the remote control device, cables,
etc.

001A Current detector fault
The current detector is defective. Contact your Toshiba distributor.

001B Optional unit fault 1
An optional device has failed.
(such as a communication device)
Check the connection of optional board.

001C Remote keypad
disconnection fault
After run signal is activated by RUN key
of the remote keypad, disconnection is
occurred in 10 seconds or more.
In case the remote keypad is
disconnected, press STOP key before.
This fault is disabled by f731=1
setting.
*

001D Low-current
operation
Trip
The output current decreased to a low-
current detection level during operation.
Enable  (low-current detection).
Check the suitable detection level for the
system (, , ).
Contact your Toshiba distributor if the
setting is correct.
*

001E Undervoltage trip
(main circuit)
The input voltage (in the main circuit) is
too low.
Check the input voltage.
Enable  (undervoltage trip
selection).
To take measures to momentary power
failure, set =, Regenerative
power ride-through control f302 and
Auto-restart control selection f301.
* This marking trips can be selected valid or invalid by parameters.
(Continued overleaf)

Table of Contents

Other manuals for Toshiba TOSVERT VF-MB1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-MB1 and is the answer not in the manual?

Toshiba TOSVERT VF-MB1 Specifications

General IconGeneral
BrandToshiba
ModelTOSVERT VF-MB1
CategoryInverter
LanguageEnglish

Related product manuals