2.2.2 Standard connection diagram 2
MCCB
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
RES
FM
CC
VIA PP
+
-
PA/+ PC/-
VF-MB1
*2
M
*5
FLC
FLB
FLA
*4
PB
*4
MCCB(2P)
R/L1
S/L2/N
S3
LOGIC
RC
RY
CC
+SU
Control power
supply
VIC
VIB
PB/e
*6
P24
OUT
NO
CC
*3
Ry
F
R
S1
S2
*1
SINK
SOURCE
SW1
PLC
SW2(S3)
PTC
Reset
Power circuit
Control
circuit
Motor
Forward run command
Reverse run command
Preset-speed command 1
Preset-speed command 2
Preset-speed command 3
Operation panel
RS485
connector
Voltage signal: 0-+10V
(or -10-+10V)
Current signal: 4(0)-20mA
Speed reach
signal output
Braking resistor(Option)
Protective function
activation output
Main circuit power supply
1ph-240V class: single-phase 200-240V
-50/60Hz
3ph-500V class: three-phase 380-500V
-50/60Hz
Power
supply
Single
phase
Meter
External potentiometer (1k-10k)
7.5V-1mA
(or 0-10V/4-20mA)
Frequency
met er
(ammet er )
(or voltage signal between VIA and CC: 0-10V)
Standard connection diagram - SOURCE (Positive) (common:P24)
Noise
filter
Low-speed
signal output
STO
Common
*2: The T/L3 terminal is not provided for
single-phase models.
Use the R/L1 and S/L2/N terminals as
input terminals.
*3: When using the NO output terminal in
source logic mode, short the P24 and
OUT terminals.
*5: To supply control power from an external
power supply for backing up the control
power supplied from the inverter, an optional
control power backup device (CPS002Z) is
required. In such a case, the backup device
is used at the same time with the internal
power supply of the inverter.
The optional control power backup unit can
be used with both 200V and 400V models.
*4: When VIA or VIB terminal is used as logic
input terminal, refer to section 7.2.1.
*1: Set the slide switch SW1 to source side.
Refer to page B-11,12 for details.
Default setting is PLC side.
*6: When STO terminal is used as compliance with
safety standards, refer to section 9.3.