Diagnostics
RTHD-SVX02H-EN 113
Table 35. Diagnostics Table
Hex
Code
Diagnostic Name
and Source
Severity Persistence Criteria Reset
Level
6B6 Comm Loss: Oil Re-
turn Gas Pump Drain
Normal Latch Continual loss of communication between the MP and the Func-
tional ID has occurred for a 30 second period.
Remote
6B6 Comm Loss: Oil Re-
turn Gas Pump Fill
Normal Latch Continual loss of communication between the MP and the Func-
tional ID has occurred for a 30 second period.
Remote
6A0 Comm Loss: Op Sta-
tus Programmable
Relays
Info Latch Continual loss of communication between the MP and the Func-
tional ID has occurred for a 30 second period.
Remote
5E2 Comm Loss: Outdoor
Air Temperature
Info and Spe-
cial Action
Latch Continual loss of communication between the MP and the Func-
tional ID has occurred for a 30 second period. Note that if this
diagnostic occurs, Chiller shall remove any OA Chilled Water
Reset, if it was in effect and if Tracer OA was unavailable. Apply
slew rates per Chilled Water Reset spec
Remote
6B6 Comm Loss: Refrig-
erant Monitor Input
Info Latch Continual loss of communication between the MP and the Func-
tional ID has occurred for a 30 second period.
Remote
5D2 Comm Loss: Slide
Valve Load
Normal Latch Continual loss of communication between the MP and the Func-
tional ID has occurred for a 30 second period.
Remote
5D1 Comm Loss: Slide
Valve Unload
Normal Latch Continual loss of communication between the MP and the Func-
tional ID has occurred for a 30 second period.
Remote
6B6 Comm Loss: Solid
State Starter Fault
Input
Info Latch Continual loss of communication between the MP and the Func-
tional ID has occurred for a 30 second period.
Remote
690 Comm Loss: Starter Immediate Latch Continual loss of communication between the MP and the Func-
tional ID has occurred for a 30 second period.
Local
1F5 Compressor Did Not
Accelerate Fully
Immediate Latch The starter module did not receive an “Up to Speed” or “End of
Ramp” signal from the SSS within 2.5 seconds after commanding
a bypass, or after the maximum acceleration time had expired,
whichever is longer. This diagnostic only applies to SSS.
Local
EE Compressor Did Not
Accelerate: Shut-
down
Immediate Latch The compressor did not come up to speed (get to <85%RLA) in
the allotted time dened by the Maximum Acceleration Timer and
and the start was aborted per the starter conguration selected.
Remote
1FA Compressor Did Not
Accelerate: Transi-
tion
Info Latch The compressor did not come up to speed (get to <85%RLA) in
the allotted time dened by the Maximum Acceleration Timer and
a transition was forced (motor put across the line) at that time.
This applies to all starter types. Note: Since RTHD SSS has no
forced transition capability, this info warning can be followed with
a “Compressor did not accelerate fully “ diagnostic above and an
aborted start.
Remote
284 Compressor Dis-
charge Temperature
Sensor
Immediate Latch Bad Sensor or LLID Remote
9A Condenser Entering
Water Temperature
Sensor
Info and Spe-
cial Action
Latch Bad Sensor or LLID. If chiller running, and condenser water regu-
lating valve option installed, force valve to 100% ow.
Remote
9B Condenser Leaving
Water Temperature
Sensor
Info Latch Bad Sensor or LLID Remote
5B8 Condenser Refriger-
ant Pressure Trans-
ducer
Normal Latch Bad Sensor or LLID Remote
F7 Condenser Water
Flow Lost
Immediate NonLatch The condenser water ow proof input was open for more than 6
contiguous seconds after ow had been proven. This diagnostic is
automatically cleared once the compressor is stopped by a xed
time out of 7 sec. The Cond Pump shall be commanded off but
the Evap pump command will not be effected.
Remote
DC Condenser Water
Flow Overdue
Normal NonLatch Condenser water ow was not proven within 20 minutes of the
condenser pump relay being energized. The Cond Pump shall be
commanded off. Diagnostic is reset with return of ow (although
only possible with external control of pump)
Remote
EC or
EC
Current Overload
TripMotor Current
Overload
Immediate Latch Compressor current exceeded overload time vs. trip characteris-
tic. For A/C products Must trip = 140% RLA, Must hold=125%,
nominal trip 132.5% in 30 seconds
Local
FD Emergency Stop Immediate Latch a. EMERGENCY STOP input is open. An external interlock has
tripped. Time to trip from input opening to unit stop shall be 0.1
to 1.0 seconds.
Local
8E Evaporator Entering
Water Temperature
Sensor
Info Latch Bad Sensor or LLID Normal operation unless CHW Reset is en-
abled. If CHW Reset is enabled and either Return or Constant
Return Chilled Water Reset is selected, its effect will be removed
but slew rates on the change will be limited per the Chilled Water
Reset spec.
Remote