Loading...
Operator Interface Controls
82 RTHD-SVX02H-EN
Main Display Area/Home Screen
All screens appear within the main display area (shown
as location in Figure 43).
Home screen: Chiller status information
The home screen (Figure 43) provides the most frequent-
ly needed chiller status information on “touch targets”
(the entire white rectangular areas) for each chiller com-
ponent. Touching any touch target displays a screen con-
taining more chiller status information related to each
component .
Figure 43. Main Screen
Table 23. Main Screen Items
Description Resolution Units
Active Chilled Water Setpoint X.X
°
F /
°
C
Active Current Limit Setpoint X.X %RLA
Average Motor Current %RLA X.X %RLA
Evap Entering/Leaving Water Temp X.X
°
F /
°
C
Cond Entering/Leaving Water Temp X.X
°
F /
°
C
Frequency Command X.X Hz
Evaporator Water Flow Status X.X
Condenser Water Flow Status
Viewing Chiller Operating Modes
On the Reports screen, touch Chiller Operating Modes to
view the current operating status of the chiller in terms
of the top-level operating mode and submodes.
Note: You can also access the Chiller Operating Modes
screen from the chiller status button in the upper
left corner of the screen.
Figure 44. Chiller Operating Modes screen