Diagnostics
11 8 RTHD-SVX02H-EN
Table 35. Diagnostics Table
Hex
Code
Diagnostic Name
and Source
Severity Persistence Criteria Reset
Level
3D7 Transition Complete
Input Opened
Immediate Latch The Transition Complete input is open with the compressor motor
running after a successful completion of transition. This is active
only for all electromechanical starters
Local
3D5 Transition Complete
Input Shorted
Immediate Latch The Transition Complete input is shorted before the compressor
was started. This is active for all electromechanical starters.
Local
D8 Under Voltage Normal Non Latch a. Average of all monitored Line voltages below - 10% of nomi-
nal or the Under/Overvoltage transformer( s) are not connected.
[Must hold = - 10 % of nominal. Must trip = - 15 % of nominal.
Reset differential = min. of 2% and max. of 4%. Time to trip =
min. of 1 min. and max. of 5 min.) Design: Nom. trip: 60 sec-
onds at less than 87.5%, + or - 2.8% at 200V or + or - 1.8% at
575V, Auto Reset at 90% or greater.
Remote
6B6 Heat recovery tank
temperature sensor
Alarm Latch Bad Sensor or LLID Remote
6B6 Heat recovery outlet
temperature sensor
Warning Latch Bad Sensor or LLID Remote
6B6 Heat recovery water
inlet temperature
sensor
Warning Latch Bad Sensor or LLID Remote
6B6 External heat re-
covery temperature
setting input
Warning Non Latch Bad Sensor or LLID Remote
6B6 Heat recovery ow
delay
Alarm Non Latch The water in the heat recovery pipeline cannot be proved to
be owing in 20 minutes after the heat recovery pump relay is
added. The heat recovery pump will be ordered to stop when
the heat recovery line detects the ow of water and the alarm is
cleared.
Remote
6B6 The heat recovery
ow is short
Immediate Non Latch The input disconnection of the ow of the heat recovery pipeline
is more than 6 seconds after conrming the ow. The compressor
is automatically cleared after 7 seconds.
Remote
6B6 Undesired ow -
main condenser
Warning Non Latch When the main condenser is ordered to shut down, it will con-
tinue to monitor the presence of water. Once the water ow is
detected, the alarm will be automatically cleared.
Remote
6B6 Undesired ow - heat
recovery condenser
Warning Non Latch When the heat recovery condenser is ordered to be shut down
for 180 days, it will continue to monitor the presence of water.
Once the water ow is detected, the alarm will be automatically
cleared.
Remote
6B6 No communication:
heat recovery tank
temperature
Alarm Latch Continuous communication between M P and functional ID was
interrupted for 35 to 40 seconds.
Remote
6B6 No communication:
heat recovery outlet
temperature
Warning Latch Continuous communication between M P and functional ID was
interrupted for 35 to 40 seconds.
Remote
6B6 No communication:
heat recovery water
inlet temperature
Warning Latch Continuous communication between M P and functional ID was
interrupted for 35 to 40 seconds.
Remote
6B6 No communication:
heat recovery ow
switch
Alarm Latch Continuous communication between M P and functional ID was
interrupted for 35 to 40 seconds.
Remote
6B6 No communication:
heat back pump
Warning Latch Continuous communication between M P and functional ID was
interrupted for 35 to 40 seconds.
Remote
6B6 No communication:
external heat recov-
ery Settings
Warning Latch Continuous communication between M P and functional ID was
interrupted for 35 to 40 seconds.
Remote
6B6 No communication:
external heat recov-
ery command
Warning Latch Continuous communication between M P and functional ID was
interrupted for 35 to 40 seconds.
Remote