Table 6. General Data
Unit Designator (corresponds to digits 6, 7, 14, 15, 21, 22 of unit model number)
C1C2D2 C1D6E5 C1D5E4 C1D3E3 C1E1F1 C2D4E4 C2D3E3
General
Refrigerant Type HFC-134a HFC-134a HFC-134a HFC-134a HFC-134a HFC-134a HFC-134a
Refrigerant Charge
(lb (kg))
490
(222)
490
(222)
490
(222)
490
(222)
525
(238)
490
(222)
490
(222)
Oil Charge
(gal(l))
6
(23)
6
(23)
6
(23)
6
(23)
10
(38)
6
(23)
6
(23)
Operating Weight
(lb(kg))
12460
(5652)
13397
(6077)
13673
(6202)
15044
(6824)
15818
(7175)
13672
(6202)
15044
(6824)
Shipping Weight
(lb(kg))
11735
(5334)
12780
(5797)
12973
(5885)
14002
(6351)
14718
(6675)
12972
(5884)
14002
(6351)
Overall Dimensions
Length
(in(mm))
145
(3674)
130
(3313)
130
(3313)
130
(3313)
146
(3712)
130
(3313)
130
(3313)
Width
(in(mm))
67
(1695)
68
(1717)
68
(1717)
68
(1717)
68
(1717)
68
(1717)
68
(1717)
Height
(in(mm))
74
(1870)
76
(1937)
76
(1937)
76
(1937)
76
(1937)
76
(1937)
76
(1937)
Evaporator
Water Storage
(gal (l))
58
(220)
45
(170)
52
(197)
78
(295)
82
(311)
52
(197)
78
(295)
Minimum Flow
(gpm (l/s))
Water
347 (22) for
2-pass
293 (18) for
2-pass
351 (21) for
2-pass
465 (31) for
2-pass
450 (28) for
2-pass
351 (21) for
2-pass
465 (31) for
2-pass
232 (15) for
3-pass
196 (12) for
3-pass
234 (15) or
3-pass
324 (20) or
3-pass
300 (19) for
3-pass
234 (15) or
3-pass
324 (20) for
3-pass
Minimum Flow
(gpm (l/s))Brine
375 (24) for
2-pass
352 (22) for
2-pass
422 (27) for
2-pass
584 (37) for
2-pass
487 (31) for
2-pass
422 (27) for
2-pass
584 (37) for
2-pass
276 (17) for
3-pass
233 (15) for
3-pass
281 (18) or
3-pass
389 (25) or
3-pass
357 (23) for
3-pass
281 (18) for
3-pass
389 (25) for
3-pass
Maximum Flow
(gpm (l/s))
1531 (97) for
2-pass
1287 (81) for
2-pass
1542 (97)or
2-pass
2131 (134)or
2-pass
1980 (125)
for
2-pass
1542 (97) for
2-pass
2131 (134)
for
2-pass
1022 (150)
for
3-pass
860 (54) for
3-pass
1028 (65) or
3-pass
1417 (89) or
3-pass
1320 (83) for
3-pass
1028 (65) for
3-pass
1417 (89) for
3-pass
Condenser (all are 2-pass)
Water Storage
(gal (l))
34
(129)
29
(110)
32
(121)
47
(178)
60
(226)
32
(121)
47
(178)
Minimum Flow
(gpm (l/s))Water
212
(13)
206
(13)
245
(15)
325
(21)
375
(24)
245
(15)
325
(21)
Minimum Flow
(gpm (l/s))Brine
255
(16)
250
(16)
295
(19)
390
(25)
450
(28)
295
(19)
390
(25)
Max Flow
(gpm (l/s))
935
(59)
910
(57)
1080
(68)
1420
(90)
1650
(104)
1080
(68)
1420
(90)
All weights ±3%, include standard 150 psig water boxes.
Operating weights include refrigerant, oil, and water charges.
If oil cooler is installed, add 1/4 gal (1 liter) to the oil charge value given for B family units; add 1.0 gal (4 liters) for all other units.
Overall dimensions are based on 3-pass evap/2 congurations pass cond and LH/RH water connections. Refer to TOPSS for exact job congu-