RLC-SVX19G-GB
135
11UNT-PRC002-GB
Sound power levels
Discharge
Measurement conditions:
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) fixed to its discharge opening.
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 55 50 42 37 37 31 30 46
FWD 08 2 57 54 47 40 30 38 40 50
3 58 57 50 42 32 40 43 53
1 57 51 45 42 34 33 28 48
FWD 10 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 57 51 45 42 34 33 28 48
FWD 12 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 56 62 50 48 39 38 36 56
FWD 14 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
1 57 63 51 49 40 39 37 57
FWD 20 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
Intake
Measurement conditions:
Measurements taken at the horizontal air intake.
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 56 55 55 53 46 45 42 57
FWD 08 2 63 62 60 60 53 53 53 64
3 66 65 63 62 56 55 57 67
1 62 58 55 58 51 48 44 61
FWD 10 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 62 58 55 58 51 48 44 61
FWD 12 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 66 65 65 65 57 50 46 68
FWD 14 2 73 72 69 71 64 59 57 74
3 78 76 73 75 69 64 63 78
1 68 72 64 64 56 52 50 69
FWD 20 2 76 76 68 71 65 61 61 75
3 78 79 71 74 69 66 66 78
Figure 24 – Flow chart - Free cooling - Glycol free version
123
4
A
B
ITEM DESIGNATION
1 DRY COOLER COILS
2 PUMP
3 MODULATING VALVE
4 DRAIN VALVE
5 BPHE
6 EXPANSION TANK
7 PRESSURE RELIEF VALVE
8 ANTIFREEZE PROTECTION
9 EVAPORATOR
10
BYPASS MANUAL VALVE
(PARTIAL FREE COOLING ONLY)
ITEM DESIGNATION
TT TEMPERATURE SENSOR
TT TT
TT
4
4
7
1
9
3
4
TT
TT
8
2
6
5
8
10
Note: glycol free cooling chilled water setpoint should be in the range of [4°C - 20° C]. Glycol is filled on the free
cooling coils on valve item 4 (3/4”).
Optional Free-Cooling

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane Sintesis RTAF HE series and is the answer not in the manual?

Trane Sintesis RTAF HE series Specifications

General IconGeneral
BrandTrane
ModelSintesis RTAF HE series
CategoryChiller
LanguageEnglish

Related product manuals