RLC-SVX19G-GB
164
4 UNT-PRC002-GB
Technical Data
FWD 08 12 20 30 45
Power supply (V/Ph/Hz) 230/1/50
Capacities
Cooling capacity on water (1) (kW) 5,2 8,3 15 18,8 30,1
Heating capacity on water (2) (kW) 6,3 11,9 18,9 20,9 38,2
Fan motor (type) 2 x direct drive centrifugal
Fan power input (3) (kW) 0,23 0,46 0,65 1,04 1,51
Current amps (3) (A) 1,1 2,2 3,1 4,7 5,5
Start-up amps (A) 3,2 5,5 9,3 14,1 16,5
Air flow
minimum (m
3
/h) 490 980 1400 1800 2700
nominal (m
3
/h) 820 1650 2300 3000 4500
maximum (m
3
/h) 980 1970 2600 3600 5400
Main coil
Water entering/leaving connections (type) ISO R7 rotating female
(Dia) 3/4" 3/4" 1 1/2" 1 1/2" 1 1/2"
Electric heater (accessory for blower only)
Electric power supply (V/Ph/Hz) 230/1/50 230/1/50 or 400/3/50 400/3/50 400/3/50 400/3/50
Heating capacity (kW) 2/4 8 10 12 12
Hot water coil (accessory for blower only)
Heating capacity (4) (kW) 6,3 12 17,4 22,4 34,5
G2 filter (filter box accessory)
Quantity 2 2 2 2 2
Dimensions ( LxWxth) (mm) 386x221x8 486x271x8 586x321x8 586*421*8 586*621*8
G4 filter (filter box accessory)
Quantity - 2 2 2 2
Dimensions ( LxWxth) (mm) - 486x264x48 586x314x48 586*414*48 586*614*48
Condensate pump (accessory) (type) Centrifugal
Water flow - lift height (l/h - mm) 24 - 500
Not available for FWD30 and FWD45
Sound level (L/M/H speed)
Sound pressure level (5) (dB(A)) 36/40/43 38/41/44 46/50/53 47/52/57 47/52/58
Sound power level (5) (dB(A)) 46/50/53 48/51/54 56/60/63 57/62/67 57/62/68
Unit dimensions
Width x Depth (mm) 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090
Height (mm) 250 300 350 450 650
Shipped unit dimensions
Width x Depth (mm) 933 x 644 1133 x 754 1333 x 864 1333 x 1008 1333*1133
Height (mm) 260 310 360 460 660
Weight (kg) 32 46 61 76 118
Colour galvanised steel
Recommended fuse size
Unit alone (aM/gI) (A) 8/16 8/16 8/16 8/25 8/25
Unit with electric heater (gI) (A) 16 (2kW),25 (4kW) 40 (230V),3*16 (400V) 3*20 3*25 3*25
(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
(3) At high speed with nominal air flow.
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.
Heat exchanger operating limits:
FWD:
*water temperature: max 100° C
*absolute service pressure: min 1 bar/max 11 bars
Accessories - Hot water coil:
*water temperature: min. +2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars
Unit Start Up Procedures
CAUTION! To prevent damage to the compressor, ensure
that all refrigerant valves are open before starting the
unit. Do not use untreated or improperly treated water.
Equipment damage may occur.
Temporary Shutdown and Restart
Temporary Shutdown is used for control operation,
maintenance or to repair the unit typically less than one
week.
To shut the unit down for a short time, use the following
procedure:
1. Press the STOP key on the TD7. The compressors
will continue to operate and, after unloading for
20 seconds, will stop when the compressor
contactors de-energize.
2. Stop the water circulation by turning off the chilled
water pump at least one minute after the stop of the
compressors.
To restart the unit after a temporary shutdown, enable the
chilled-water pump and press the AUTO key.
The unit will start normally, provided the following
conditions exist:
The UC800 receives a call for cooling and the
differential-to-start is above the set point
All system operating interlocks and safety circuits are
satisfied
CAUTION! Under freezing conditions, the chilled water
pump must remain in operation during the full shutdown
period of the chiller if the chilled water loop does not
contain glycol, to prevent any risk of evaporator freeze-
up. Refer to charts 1 and 2.
Extended Shutdown Procedure
The following procedure is to be followed if the system
is to be taken out of service for an extended period of
time (i.e. seasonal shutdown):
1. Test the unit for refrigerant leaks and repair as
necessary
2. Open the electrical disconnect switches for the
chilled-water pump. Lock the switches in the OPEN”
position.
3. Close all chilled-water supply valves. Drain the water
from the evaporator.
4. Open the unit main electrical disconnect and unit-
mounted disconnect (if installed) and lock in the
OPEN” position.
5. At least every three months (quarterly), check
the refrigerant pressure in the unit to verify the
refrigerant charge integrity.
6. Optional pump. The pump is maintenance-free. If the
pump is to be drained for a long period of inactivity,
inject a few drops of silicone oil on the shaft between
the motor stool and the coupling. This will present
the shaft seal faces from sticking.
CAUTION! Lock the chilled-water pump disconnects open
to prevent pump damage. Lock the disconnect switch
in the OPEN” position to prevent accidental startup
and damage to the system when it has been set up for
extended shutdown.
During an extended shutdown period, especially over the
winter season, the evaporator must be drained of water,
if the chilled water loop does not contain glycol,
to prevent any risk of evaporator freeze-up.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane Sintesis RTAF HE series and is the answer not in the manual?

Trane Sintesis RTAF HE series Specifications

General IconGeneral
BrandTrane
ModelSintesis RTAF HE series
CategoryChiller
LanguageEnglish

Related product manuals