3-13 Reference Site
Option: Function:
Select which reference site to activate.
[0] * Linked to Hand / Auto Use local reference when in hand mode; or remote reference when in
auto mode.
[1] Remote Use remote reference in both hand mode and auto mode.
[2] Local Use local reference in both hand mode and auto mode.
NOTE
When set to Local [2], the adjustable frequency drive will start with this setting
again following a '
power-down'.
3-14 Preset Relative Reference
Range: Function:
0.00 %* [-100.00 - 100.00 %]
3-15 Reference 1 Source
Option: Function:
Select the reference input to be used for the first reference signal. par.
3-15
Reference 1 Source, par.3-16 Reference 2 Source and par.3-17 Ref-
erence 3 Source define up to three different reference signals. The sum
of these reference signals defines the actual reference.
This parameter cannot be adjusted while the motor is running.
[0] No function
[1] * Analog input 53
[2] Analog input 54
[7] Pulse input 29
[8] Pulse input 33
[20] Digital pot.meter
[21] Analog input X30/11
Parameter Description
TR200 Programming Guide 4-39