[10] Reverse
[11] Start reverse
[14] Jog
[15] Preset reference on
[16] Preset ref bit 0
[17] Preset ref bit 1
[18] Preset ref bit 2
[19] Freeze reference
[20] Freeze output
[21] Speed up
[22] Slow
[23] Set-up select bit 0
[24] Set-up select bit 1
[34] Ramp bit 0
[36] Mains failure inverse
[37] Fire Mode
[52] Run permissive
[53] Hand start
[54] Auto-start
[55] DigiPot increase
[56] DigiPot decrease
[57] DigiPot clear
[62] Reset Counter A
[65] Reset Counter B
[66] Sleep Mode
[78] Reset Maint. Word
[120] Lead Pump Start
[121] Lead Pump Alternation
[130] Pump 1 Interlock
[131] Pump 2 Interlock
[132] Pump 3 Interlock
5-3* Digital Outputs
Parameters for configuring the output functions for the output terminals. The 2 solid-state digital outputs are
common for terminals 27 and 29. Set the I/O function for terminal 27 in par.5-01
Terminal 27 Mode and set the
I/O function for terminal 29 in par.5-02
Terminal 29 Mode. These parameters cannot be adjusted while the motor
is running.
The digital outputs can be programmed with these functions:
[0] No operation
Default for all digital outputs and relay outputs
[1] Control ready The control board receives supply voltage.
[2] Drive ready The adjustable frequency drive is ready for operation and applies a sup-
ply signal on the control board.
Parameter Description
4-66 TR200 Programming Guide