IT line power
WARNING
Do not connect adjustable frequency drives with RFI filters to line power supplies with a voltage between phase and
ground of more than 440 V for 400 V drives and 760 V for 690 V drives.
For 400 VT IT lin
e power and delta ground (grounded leg), AC line voltage may exceed 440 V between phase and ground.
Fo
r 690 VT IT line power and delta ground (grounded leg), AC line voltage may exceed 760 V between phase and ground.
Failure to follow recommendations could result in death or serious injury.
par.14-50
RFI 1 can be used to disconnect the internal RFI capacitors from the RFI filter to ground.
Software Version and Approvals: TR200
TR200
Software version: 1.1.x
This manual can be used with all TR200 adjustable frequency drives with software version 1.1.x.
The software version number can be seen from par.15-43
Software Version.
Equipment containing electrical components may not be disposed of together
with domestic waste.
It must be separately collected with electrical and electronic waste according to
local and currently valid legislation.
TR200 Programming Guide 1-5