Main Menu - Analog In/Out - Group 6
6-** Analog In/Out
Parameter group for configuring the analog input and output.
Parameter group for setting up the analog I/O configuration.
The adjustable frequency drive is equipped with 2 analog inputs: Terminal 53 and 54. The analog inputs can
freely be allocated to either voltage (0–10 V) or current input (0/4–20 mA)
NOTE
Thermistors may be connected to either an analog or a digital input.
6-00 Live Zero Timeout Time
Range: Function:
10 s* [1 - 99 s] Enter the Live Zero Timeout time period. Live Zero Timeout Time is active
for analog inputs, i.e., terminal 53 or terminal 54, used as reference or
feedback sources. If the reference signal value associated with the se-
lected current input falls below 50% of the value set in par.6-10
Terminal
53 Low Voltage, par.6-12 Terminal 53 Low Current, par.6-20 Terminal 54
Low Voltage or par.6-22 Terminal 54 Low Current for a time period longer
than the time set in par.6-00
Live Zero Timeout Time, the function selec-
ted in par.6-01
Live Zero Timeout Function will be activated.
6-01 Live Zero Timeout Function
Option: Function:
Select the timeout function. The function set in par.6-01
Live Zero Time-
out Function will be activated if the input signal on terminal 53 or 54 is
below 50% of the value in par.6-10
Terminal 53 Low Voltage, par.
6-12
Terminal 53 Low Current, par.6-20 Terminal 54 Low Voltage or par.
6-22
Terminal 54 Low Current for a time period defined in par.6-00 Live
Zero Timeout Time. If several timeouts occur simultaneously, the ad-
justable frequency drive prioritizes the timeout functions as follows:
1. par.6-01
Live Zero Timeout Function
2. par.8-04
Control Timeout Function
The output frequency of the adjustable frequency drive can be:
• [1] frozen at the present value
• [2] overruled to stop
• [3] overruled to jog speed
• [4] overruled to max. speed
• [5] overruled to stop with subsequent trip
[0] * Off
[1] Freeze output
[2] Stop
[3] Jogging
TR200 Programming Guide 4-83