[40] Set digital out C high Any output with ‘digital output 3’ selected is high (closed).
[41] Set digital out D high Any output with ‘digital output 4’ selected is high (closed).
[42] Set digital out E high Any output with ‘digital output 5’ selected is high (closed).
[43] Set digital out F high Any output with ‘digital output 6’ selected is high (closed).
[60] Reset Counter A Resets Counter A to zero.
[61] Reset Counter B Resets Counter A to zero.
[70] Start Timer 3 Starts timer 3, see par.13-20
SL Controller Timer for further description.
[71] Start Timer 4 Starts timer 4, see par.13-20
SL Controller Timer for further description.
[72] Start Timer 5 Starts timer 5, see par.13-20
SL Controller Timer for further description.
[73] Start Timer 6 Starts timer 6, see par.13-20
SL Controller Timer for further description.
[74] Start Timer 7 Starts timer 7, see par.13-20
SL Controller Timer for further description.
[80] Sleep Mode
Main Menu - Special Functions -Group 14
14-** Special Functions
Parameter group for configuring special adjustable frequency drive functions.
Parameters for configuring the .
14-00 Switching Pattern
Option: Function:
Select the switching pattern: 60° AVM or SFAVM.
[0] * 60 AVM
[1] SFAVM
14-01 Switching Frequency
Option: Function:
Select the inverter switching frequency. Changing the switching fre-
quency can help to reduce acoustic noise from the motor.
NOTE: The output frequency value of the adjustable frequency drive
must never exceed 1/10 of the switching frequency. When the motor is
running, adjust the switching frequency in par.14-01
Switching Frequen-
cy until the motor is as noiseless as possible. See also par.14-00 Switch-
ing Pattern and the section
Derating
.
[0] 1.0 kHz
[1] 1.5 kHz
[2] 2.0 kHz
[3] 2.5 kHz
[4] 3.0 kHz
[5] 3.5 kHz
4-120 TR200 Programming Guide