[3] Select set-up 2 Changes the active set-up (par.0-10 Active Set-up) to ‘2’.
[4] Select set-up 3 Changes the active set-up (par.0-10
Active Set-up) to ‘3’.
[5] Select set-up 4 Changes the active set-up (par.0-10
Active Set-up) to ‘4’. If the set-up is
changed, it will merge with other set-up commands coming from either
the digital inputs or via a serial communication bus.
[10] Select preset ref 0 Selects preset reference 0.
[11] Select preset ref 1 Selects preset reference 1.
[12] Select preset ref 2 Selects preset reference 2.
[13] Select preset ref 3 Selects preset reference 3.
[14] Select preset ref 4 Selects preset reference 4.
[15] Select preset ref 5 Selects preset reference 5.
[16] Select preset ref 6 Selects preset reference 6.
[17] Select preset ref 7 Selects preset reference 7. If the active preset reference is changed, it will
merge with other preset reference commands coming from either the
digital inputs or via a serial communication bus.
[18] Select ramp 1 Selects ramp 1
[19] Select ramp 2 Selects ramp 2
[22] Run Issues a start command to the adjustable frequency drive.
[23] Run reverse Issues a start reverse command to the adjustable frequency drive.
[24] Stop Issues a stop command to the adjustable frequency drive.
[26] Dcstop Issues a DC stop command to the adjustable frequency drive.
[27] Coast The adjustable frequency drive coasts immediately. All stop commands
including the coast command stop the SLC.
[28] Freeze output Freezes the output frequency of the adjustable frequency drive.
[29] Start timer 0 Starts timer 0, see par.13-20
SL Controller Timer for further description.
[30] Start timer 1 Starts timer 1, see par.13-20
SL Controller Timer for further description.
[31] Start timer 2 Starts timer 2, see par.13-20
SL Controller Timer for further description.
[32] Set digital out A low Any output with ‘digital output 1’ selected is low (off).
[33] Set digital out B low Any output with ‘digital output 2’ selected is low (off).
[34] Set digital out C low Any output with ‘digital output 3’ selected is low (off).
[35] Set digital out D low Any output with ‘digital output 4’ selected is low (off).
[36] Set digital out E low Any output with ‘digital output 5’ selected is low (off).
[37] Set digital out F low Any output with ‘digital output 6’ selected is low (off).
[38] Set digital out A high Any output with ‘digital output 1’ selected is high (closed).
[39] Set digital out B high Any output with ‘digital output 2’ selected is high (closed).