Main Menu - LonWorks - Group 11
LonWorks, 11-**
Parameter group for all LonWorks specific parameters.
Parameters related to LonWorks ID.
11-00 Neuron ID
Range: Function:
0 N/A* [0 - 0 N/A] View the Neuron chip's unique Neuron ID number.
11-01 Domain
Range: Function:
0 N/A* [0 - 0 N/A]
11-02 Subnet ID
Range: Function:
0 N/A* [0 - 255 N/A]
11-03 Node ID
Range: Function:
0 N/A* [0 - 255 N/A]
11-10 Drive Profile
Option: Function:
This parameter allows selecting between LONMARK Functional Profiles.
[0] * VSD profile The Trane Profile and the Node Object are common for all profiles.
[1] Pump controller
11-15 LON Warning Word
Range: Function:
0 N/A* [0 - 65535 N/A] This parameter contains the LON specific warnings.
Bit Status
0 Internal fault
1 Internal fault
2 Internal fault
3 Internal fault
4 Internal fault
5 Invalid type change for nvoAnIn1
6 Invalid type change for nvoAnIn2
7 Invalid type change for nvo109AnIn1
8 Invalid type change for nvo109AnIn2
9 Invalid type change for nvo109AnIn3
10 Initialization error
11 Internal communication error
12 Software revision mismatch
13 Bus not active
14 Option not present
15 LON input (nvi/nci) exceeds limits