Parameter [Units]
par.0-01 Language
par.1-20 Motor Power [kW] [kW]
par.1-21 Motor Power [HP] [HP]
par.1-22
Motor Voltage* [V]
par.1-23 Motor Frequency [Hz]
par.1-24
Motor Current [A]
par.1-25 Motor Nominal Speed [RPM]
par.1-28
Motor Rotation Check [Hz]
par.3-41 Ramp 1 Ramp-up Time [s]
par.3-42
Ramp 1 Ramp-down Time [s]
par.4-11 Motor Speed Low Limit [RPM] [RPM]
par.4-12
Motor Speed Low Limit [Hz]*[Hz]
par.4-13 Motor Speed High Limit [RPM] [RPM]
par.4-14
Motor Speed High Limit [Hz]*[Hz]
par.3-19 Jog Speed [RPM] [RPM]
par.3-11
Jog Speed [Hz]*[Hz]
Par.5-12 Terminal 27 Digital Input
par.5-40
Function Relay**
Table 3. 1: Quick Set-up parameters
*The display showing depends on choices made in
par.0-02
Motor Speed Unit and par.0-03 Regional Set-
tings. The default settings of par.0-02 Motor Speed
Unit and par.0-03 Regional Settings depend on which
region of the world the adjustable frequency drive is
supplied to but can be re-programmed as required.
** par.5-40
Function Relay, is an array, where one
may choose between Relay1 [0] or Relay2 [1]. Stand-
ard setting is Relay1 [0] with the default choice Alarm
[9].
See the parameter description in the section
Com-
monly Used Parameters
.
For a detailed information about settings and programming, please see the
TR200 Programming Guide
NOTE: If [No Operation] is selected in par.5-12 Terminal 27 Digital Input, no connection to +24 V on terminal 27
is necessary to enable start.
If [Coast Inverse] (factory default value) is selected in par.5-12
Terminal 27 Digital Input, a connection to +24 V
is necessary to enable start.
The Function set-up provides quick and easy access to all parameters required for the majority of TR200 appli-
cations including most VAV and CAV supply and return fans, cooling tower fans, primary, secondary and
condenser water pumps and other pump, fan and compressor applications.
3-10 TR200 Programming Guide